Class 1 Div 1 certified Intrinsically Safe true wireless system powers HART, 4-20mA, 1-5V and DI sensors from internal battery with 1 mile range.
|
Operating Temp |
-40C to 60C |
|
Humidity |
0% - 100% Condensing |
|
Power |
3 X D LithiumBatteryPack. Field Replaceable. Class 1, Division 1 Certified when used with SignalFire System. In Situ replacement does not require a work ticket. |
|
Sensor Power |
18V for 4-20 mA CurrentLoopor Hart Sensors. Sensor power is provided from the system, no need for external sensor power, no barriers required if used in compliance with control drawings. |
|
BatteryLife |
1-4 years depending on the number and type of sensors and reporting frequency |
|
Data Interface |
Wireless – Available as Modbus Registers at Gateway |
|
Supported Sensor Interfaces |
Hart (up to 4 devices), 4-20 mA Current Loop, 1-5 Volt, Digital Input (State, Counter ,Totals, Frequency), Digital Output (TTL Level) |
|
Display |
Externally visible display shows communications status and sensor readings |
|
Data Update Rates |
User Selectable Rotary Switch from 5 sec to 2 hours |
|
Radio Power |
10 mW |
|
Antenna Type |
External Weather Resistant, Omnidirectional |
|
Antenna Gain |
5dB |
|
Receive Sensitivity |
-105 dB |
|
Frequency |
902-928 MHz, FHSS, License Free ISM Band Compliant with FCC Part 15 |
|
Range |
1+ Mile (Line of Sight, Real World) |
|
Networks |
Up to 64 separate networks. Rotary Switch Selectable |
|
Enclosure |
Fiberglass Reinforced UV Stabilized Plastic |
|
Intrinsically Safe |
Class 1, Division 1, Temp Code T3, Groups C&D. Conforms to UL Std. 913, Certified to Can/CSA Std C22.2 No. 157 |
|
Internal Diagnostics |
Battery Voltage, Signal Strength, Error Conditions |
Greentech » Environmental Monitoring
Industrial Applications » Tank Monitoring
Industrial Applications » Irrigation
Industrial Applications » Process Control, SCADA
Interface » Type of Inputs / Outputs » Analog
Interface » Type of Inputs / Outputs » Digital
Environment » Temperature Range » Industrial (-25°C / +65°C)
Power Supply » Battery » Operation / Standby Time